Are you looking for a quote on PS-2-2457-5? If so, please fill out the provided quote form below. The NSN (national stock number) is 5925000757892, and the part PS-2-2457-5 is circuit breaker by British Sarozal Ltd. Please enter the given detail as much as possible, this information will help us to provide you the right quote to fulfill your needs. We will get back to you in less than 15 minutes!
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-075-7892 Item Description: Circuit Breaker | 5925 | 000757892 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Ps-2-2457-5 | 2 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ADAQ | BODY LENGTH | 2.500 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.750 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.938 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.062 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.125 INCHES NOMINAL |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.359 INCHES NOMINAL |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 2 THREADED HOLE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRJ | TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 SINGLE LOCATION |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 10.000 MINIMUM SINGLE LOCATION AND 75.000 MAXIMUM SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQJX | NOMINAL THREAD SIZE | 0.190 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 75.000 NOMINAL AT 100 PCT SINGLE LOCATION AND 10.000 MINIMUM AT 125 PCT SINGLE LOCATION AND 75.000 MAXIMUM AT 125 PCT SINGLE LOCATION AND 5.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 9.000 MAXIMUM AT 200 PCT SINGLE LOCATION AND 0.700 MINIMU |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF AND FUNGUS RESISTANT AND MOISTURE RESISTANT |
FREQ | FREQUENCY IN HERTZ | 60.0 SINGLE LOCATION |
THSD | THREAD SERIES DESIGNATOR | UNF |
TTQY | TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |