Are you looking for a quote on 1922-043? If so, please fill out the provided quote form below. The NSN (national stock number) is 5925000805835, and the part 1922-043 is circuit breaker by Federal Pacific Electric Co. Please enter the given detail as much as possible, this information will help us to provide you the right quote to fulfill your needs. We will get back to you in less than 15 minutes!
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-080-5835 Item Description: Circuit Breaker | 5925 | 000805835 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
1922-043 | 3 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 9.500 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 4.125 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.375 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.190 INCHES NOMINAL |
AFJN | III FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRG | III STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
BBRJ | III SPECIAL HANDLING FEATURE | MAGNETIC |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND HANDLE LOCK |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 225.0 AMPERES AC ALL LOCATIONS AND 225.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 15000.0 AC ALL LOCATIONS AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 ROTARY |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +1300.0 TO 2500.0 AC AND +1300.0/+2500.0 DC ALL LOCATIONS |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 70.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 160.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | DUSTPROOF |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
PKDW | PACKAGED UNIT WEIGHT | 7.500 POUNDS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |