Are you looking for a quote on 72020? If so, please fill out the provided quote form below. The NSN (national stock number) is 5925001099161, and the part 72020 is circuit breaker by Lake Shore Electric Corporation. Please enter the given detail as much as possible, this information will help us to provide you the right quote to fulfill your needs. We will get back to you in less than 15 minutes!
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-109-9161 Item Description: Circuit Breaker | 5925 | 001099161 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
72020 | 2 | 9 | 3 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 17.000 INCHES NOMINAL |
ADAT | BODY WIDTH | 8.000 INCHES MINIMUM AND 8.500 INCHES MAXIMUM |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 1.031 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 14.750 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 800.0 AMPERES AC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 10000.0 AC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 280.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 950.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FEAT | SPECIAL FEATURES | MAIN CONTACTS PROTECTED BY ARCING CONTACTS,ARC BARRIERS AND MAGNETIC BLOWOUTS; MAIN CONTACTS SELF-ALIGNING,SELF-CLEANING AND REMOVABLE |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
SPCL | SPECIAL TEST FEATURES | DIELECTRIC STRENGTH MUST PASS EQUIVALENT OF 1960V BETWEEN LIVE PARTS AND GROUND AND BETWEEN POLES FOR 1 SECOND IN BOTH OPEN AND CLOSED POSITIONS; MUST INTERRUPT 350 PERCENT AT 60 HZ OF ITS RATED CURRENT AT 208V FOR 30 OPERATIONS AT 10 SECON |
Are you looking for quote within 15 minutes for your desired part? Fill an instant form and receive lowest price quote guaranteed.